Contact
Applications
The H05V-K and H07V-K cables are color-coded PVC sheathed, copper single-core stranded wires. Specially suitable for application in:
● internal wiring of distribution and switching boxes equipment
● lighting, control and power distribution control panels, ducts, channels
● in the switch control,relay and instrumentation panels of power switch gear
For any more information or advice please contact the office on 0086-18832134509(WhatsApp/WeChat)
Details
Insulated conductor is used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment. H07V-K wire implements the standards GB/T5023, equivalent to IEC60 227. And H07V-K cable can also be made complying with ASTM, DIN, BS standards etc.
Description: H05V-K&H07V-K, PVC Insulated Copper flexible Cable
Conductors: Class 5 of plain annealed flexible stranded copper in accordance with IEC 60228.
Insulation: Polyvinyl chloride PVC
Colour of Sheath: Any Colour
Voltage Rating (Uo/U) H05V-K: 300/500V H07V-K:450/750V
Test Voltage H05V-K: 2kV for 5 minutes H07V-K: 2.5kV for 5 minutes
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
300/500V H05V-K PVC Insulated flexible cable | ||||
No. of cores and nominal cross section | Thickness of Insulation | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) |
(mm2) | (mm) | (mm) | (kg/km) | (Ω/km) |
1 X 0.5 | 0.6 | 2.1 | 9 | 39.0 |
1 X 0.75 | 0.6 | 2.3 | 11 | 26.0 |
1 X 1 | 0.6 | 2.5 | 14 | 19.5 |
450/750V H07V-K PVC Insulated flexible cable | ||||
No. of cores and nominal cross section | Thickness of Insulation | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) |
1 X 1.5 | 0.7 | 2.9 | 20 | 13.3 |
1 X 2.5 | 0.8 | 3.6 | 31 | 7.98 |
1 X 4 | 0.8 | 4.1 | 45 | 4.95 |
1 X 6 | 0.8 | 4.7 | 65 | 3.30 |
1 X 10 | 1.0 | 5.9 | 109 | 1.91 |
1 X 16 | 1.0 | 6.8 | 163 | 1.2 |
1 X 25 | 1.2 | 8.4 | 251 | 0.78 |
1 X 35 | 1.2 | 9.4 | 347 | 0.554 |
1 X 50 | 1.4 | 11.0 | 493 | 0.386 |
1 X 70 | 1.4 | 12.7 | 680 | 0.272 |
1 X 95 | 1.6 | 14.7 | 910 | 0.2 |
1 X 120 | 1.6 | 16.2 | 1140 | 0.161 |
1 X 150 | 1.8 | 18.1 | 1420 | 0.129 |
1 X 185 | 2.0 | 20.2 | 1730 | 0.106 |
1 X 240 | 2.2 | 22.9 | 2270 | 0.08 |